CCE 6601 Air-Cooled Active Liquid Cooler
AC 400 / 460 V 3~, HS-Configuration
Product number:
42130655011
Pfannenberg CC6601 Chiller with the following special features:
- differential temperature control (*w/o probe), min-max temperature fluid alarm, electric level, electronic thermostat, UL 508a certified, error message, flow switch, hydraulic relief valve, non ferrous hydraulic circuit, antivibration damper, lifting eyebolt
- stand-alone chiller
- fluid cooling with water, water/glycol mixtures
- steel housing with thick powder coating
- robust industry standard with preassembled eyebolts
- reliable easy to read level indication
- mounting on top of the enclosure is possible
- separate cooling circuit and hydraulic circuit
- equipped with a programmable control module that allows small hystereses of the temperature of the cooling medium
TECHNICAL DATA
Technical Data
- Rated voltage V ±10 %
- AC 400 / 460 V 3~
- Rated frequency Hz ±1 %
- 50 Hz | 60 Hz
- Cooling capacity with pump (W18/A32)
- 6,5 kW
- Flow rate (pump)
- 15 l/min
- Pump pressure
- 2 bar
- Medium
- water/glycol - 80/20!!!
- Medium temperature range (outlet)
- +13 °C ... +35 °C
- Target value tolerance K
- ±2 K
- Refrigerant (type | amount)
- R134A | 1,4 kg
- Max power consumption kW
- 4,2 kW | 5,1 KW
- Max current consumption A
- 10 A | 9,5 A
- Starting current A
- 17,5 A | 19 A
- Control voltage V
- 24V AC
- Type of fuse | Pre fuse
- J | 12A A
- Airflow (external)
- 2.300 m3/h | 2.800 m3/h
- Tank volume
- 30 l
- Connection
- 3/4 inch
- Noise level according to EN ISO 3741 (50 Hz) dB(A)
- 74 dB(A)
- Noise level according to EN ISO 3741 dB(A)
- 74 dB(A)
- Weight (without packaging)
- 109 kg
- Protection system according to NEMA (e-box)
- IP 54
- Colour
- RAL 7035
- Dimensions (H | W | D)
- 983 mm | 600 mm | 676 mm
- Depth
- 676 mm
- Width
- 600 mm
- Height
- 983 mm
- ETIM-Class
- EC002516
- Rated voltage V ±10 %
- AC 400 / 460 V 3~
- Rated frequency Hz ±1 %
- 50 Hz | 60 Hz
- Cooling capacity with pump (W18/A32)
- 22,179 BTU/h
- Flow rate (pump)
- 4 gpm
- Pump pressure
- 29 psi
- Medium
- water/glycol - 80/20!!!
- Medium temperature range (outlet)
- +55 °F ... +95 °F
- Target value tolerance K
- ±2 K
- Refrigerant (type | amount)
- R134A | 49 oz.
- Max power consumption kW
- 4,2 kW | 5,1 KW
- Max current consumption A
- 10 A | 9,5 A
- Starting current
- 17.5 A | 19 A
- Control voltage V
- 24V AC
- Type of fuse | Pre fuse
- J | 12A A
- Airflow (external)
- 1,354 cfm | 1,648 cfm
- Tank volume
- 7 gal
- Connection
- 3/4 inch
- Noise level according to EN ISO 3741 (50 Hz) dB(A)
- 74 dB(A)
- Noise level according to EN ISO 3741 dB(A)
- 74 dB(A)
- Weight (without packaging)
- 240 lbs
- Protection system according to NEMA (e-box)
- TYPE1
- Colour
- RAL 7035
- Dimensions (H | W | D)
- 38.7 in. | 23.6 in. | 28.6 in.
- Depth
- 28.6 in.
- Width
- 23.6 in.
- Height
- 38.7 in.
- ETIM-Class
- EC002516
Technical Data
TECHNICAL DRAWINGS
Technical Drawings
Dimensions
DIAGRAMS
Diagrams
DOWNLOADS
Downloads
Description | Language | Type | Size | Link |
---|---|---|---|---|
Product_Sheet_EN_CCE_6401_6501_6601 | Englisch | 261.58 KB | Download | |
Configurations_EN_Chillers | German | 128.24 KB | Download | |
Hydraulic_Diagram_CCE | Englisch | 69.95 KB | Download | |
EAC_Certificate_Chiller | German | 932.98 KB | Download | |
Drawing_CCE_6401-6501-6601 | German | 425 KB | Download | |
Configurations_EN_Chillers | Englisch | 128.24 KB | Download | |
Hydraulic_Diagram_CCE | German | 69.95 KB | Download | |
Product_Sheet_DE_CCE_6401_6501_6601 | German | 270.33 KB | Download | |
EAC_Certificate_Chiller | Englisch | 932.98 KB | Download | |
Drawing_CCE_6401-6501-6601 | Englisch | 425 KB | Download |